We are one of the prominent and leading distributors of Cable Jointing Kits. All our products are fabricated using quality raw material and latest tools and technology at our vendors end. Our product range also includes Cold Shrink Straight Through Joints, Straight Joints and Heat Shrinkable Transition Joints. The features like efficient and sturdy performance, dimensional accuracy have made our products popular among our customers. Owing all these features
...
Read more
Size/Dimension | refer attached catalogue |
Number Of Core | single core |
Type | Straight through |
Voltage Type | High Voltage |
Core Type | Single Core |
Conductor Size | Upto 1000mm2 |
Joint Type | Straight Through |
Automation Grade | Manual |
Frequency | 50 Hz |
Cable Joint | Straight joints |
Brand | Yamuna Densons |
Packaging Type | Corrugated Box |
Voltage | Upto 36 kv |
Densons Heat Shrinkable Terminations and Straight Joints offer unsurpassed technical superiority. Using state-of-the-art manufacturing technology. Densons High Voltage products provide maximum protection against Tracking. Corona Discharge and Dielectric Stresses. Densons High Voltage Products are easily adaptable to cover a broad range of cable sizes, and conforming to various Internationally accepted standards such as IS, VDE, IEC, IEEE.
Minimum Order Quantity | 100 Unit |
Material | Heat Shrinkable Type |
Number Of Core | 1 |
Voltage | 36KV |
Brand | Yamuna Densons |
Feature | Electrolyte Grade Connector |
Corrosion Resistant | Yes |
Test Item of Heat Shrinkable Terminations as per IEC-60502-4 / IS:13573
Testing Items U o/U | 6.35/11 kV | 12.7/22 kV | 19/33 kV |
---|---|---|---|
A/C withstand test | 29kV, 5min, no flashover | 58kV, 5min, no flashover | 86kV, 5min, no flashover |
Partial discharge test | 11kV < 10pc (Max.) | 22kV < 10pc (Max.) | 33kV < 10pc (Max.) |
Thermal Cycles (63 cycles) | under95-100o C 16kV | under95-100o C 32kV | under95-100o C 48kV |
Impulse voltage test | 75kV no flashover | 125kV no flashover | 170kV no flashover |
A/C with stand test | 16kV, 15 min, no flashover | 32kV, 15 min, no flashover | 48kV, 15 min, no flashover |
Humidity test (Indoor) | No flashover, tracking erosion or mechanical damage occured at 300hrs, 8kV | No flashover, tracking erosion or mechanical damage occured at 300hrs, 16kV | No flashover, tracking erosion or mechanical damage occured at 300hrs, 24kV |
Salt Frog test (Outdoor) | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 8kV no flashover, tracking | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 16kV no flashover, tracking | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 24kV no flashover, tracking |
Type | indoor,Outdoor & Straight Through joints |
Size | 400mm2 |
Number Of Core | 3 core |
Brand | Yamuna Densons |
Core Type | 3 core |
Packaging Type | Corrugated Box |